South African Wire Size Calculator
Estimate the minimum copper conductor size for AC and DC circuits in South Africa. Enter your load, supply and distance to see the smallest standard cable that can carry the current safely and keeps voltage drop within SANS 10142-1 limits.
1. Circuit Inputs
Lighting and mixed socket circuits (SANS 10142-1 maximum of 5%)
V
A
m
Enter the single run length from the board to the load.
The cable must carry 20 A without overheating and keep the voltage drop within 5.0% of the supply voltage. Copper resistivity is taken at its 70 °C operating temperature (0.0225 Ω·mm²/m).
2. Recommended Cable Size
Minimum for current (20 A)
2.5 mm²
Minimum for voltage drop
1.57 mm²
Use at least a 2.5 mm² copper conductor. This size is needed for both the current and the voltage drop. Voltage drop will be around 3.13%.
Voltage drop at this size
7.2 V
Allowed drop (5.0%)
11.5 V
Cable current rating
24 A
How we calculate
Current: the smallest size whose current rating is at least 20 A (PVC-insulated copper in conduit, 30 °C ambient, 2 loaded conductors).
Voltage drop: A = (k × ρ × I × L) / ΔV, where k = 2.000, ρ = 0.0225 Ω·mm²/m, I = 20 A, L = 20 m and ΔV is the allowable drop for the selected load type.
The recommendation is the larger of the two.
Voltage Drop Limits
| Load type | Max drop | Examples |
|---|---|---|
| General purpose circuits | 5.0% | Lighting and mixed socket circuits (SANS 10142-1 maximum of 5%) |
| Motors / HVAC | 3.0% | Motors, compressors and pumps (3% recommended for reliable starting) |
| Sensitive electronics | 2.0% | UPS, control circuits and instrumentation (2% recommended) |
Standard Copper Cable Sizes (mm²)
1.52.54610162535507095120150185240
This tool provides guidance only. Current ratings assume a single circuit in conduit at 30 °C. Higher ambient temperatures, grouped cables or thermal insulation reduce the rating. Size the cable to the circuit breaker rating, not just the load, and verify against the full requirements of SANS 10142-1 before installation.