South African Wire Size Calculator

Estimate the minimum copper conductor size for AC and DC circuits in South Africa. Enter your load, supply and distance to see the smallest standard cable that can carry the current safely and keeps voltage drop within SANS 10142-1 limits.

1. Circuit Inputs

Lighting and mixed socket circuits (SANS 10142-1 maximum of 5%)

V
A
m

Enter the single run length from the board to the load.

2. Recommended Cable Size

Minimum for current (20 A)
2.5 mm²
Minimum for voltage drop
1.57 mm²
Voltage drop at this size
7.2 V
Allowed drop (5.0%)
11.5 V
Cable current rating
24 A

How we calculate

Current: the smallest size whose current rating is at least 20 A (PVC-insulated copper in conduit, 30 °C ambient, 2 loaded conductors).

Voltage drop: A = (k × ρ × I × L) / ΔV, where k = 2.000, ρ = 0.0225 Ω·mm²/m, I = 20 A, L = 20 m and ΔV is the allowable drop for the selected load type.

The recommendation is the larger of the two.

Voltage Drop Limits

Load typeMax dropExamples
General purpose circuits5.0%Lighting and mixed socket circuits (SANS 10142-1 maximum of 5%)
Motors / HVAC3.0%Motors, compressors and pumps (3% recommended for reliable starting)
Sensitive electronics2.0%UPS, control circuits and instrumentation (2% recommended)
Standard Copper Cable Sizes (mm²)

1.52.54610162535507095120150185240