Power Quality · Power factor correction (floor standing systems)

PF FLOOR MNT SYSTEM 213 KVAR 400V

SKU FMS21304

R 112 240.00incl. VAT

Quantity:
1

Specifications

Category
Power Quality
Sub-category
Power factor correction (floor standing systems)
Product code
FMS21304
KVAR
213
Type
Assembly/Bill of Materials
DEPTH
630mm
WIDTH
600mm
HEIGHT
2180mm
HARMONICS
No
Sub Category
Power factor correction (floor standing systems)
Pricing Group
CAT F

Detailed Description

Power factor systems (automatic) 400/440V

For applications with varying capacitor requirements. An automatic reactive controller monitors the network and only switches capacitor banks when required, avoiding potential over or under compensation in a network.

FMS series - Floor standing systems

Complete ready-to-install system comprising following:

  • Mains isolator, door interlocking (with early make/late break auxiliary contact)
  • Suitably ventilated floor standing enclosure (thermostatically controlled roof mounted exhaust fan)
  • High end reactive control relay DCRG 8 (incorporating digital display of all important network parameters)

Able to monitor all three phase voltage and current to providing accurate indication of:

  • Internal panel temperature monitoring
  • Calendar-clock with backup reserve power
  • Current and Voltage Harmonics analysis (up to 31st harmonic)
  • Active, Apparent Power as well as Active, Reactive, Apparent Energy monitoring
  • Event logging: alarms, setup changes, events etc. (internal memory stores last 250 events)

Expandable with up to 4 expansion modules for:

  • additional steps, analog Inputs/Outputs, RS323
  • RS485, Ethernet, GPRS/GSM modem communication
SERIESFMS series
KVAR AT 400V212.5
KVAR AT 440V255
STEPS (KVAR) AT 400V 12.51
STEPS (KVAR) AT 400V 252
STEPS (KVAR) AT 400V 503
STEPS (KVAR) AT 400V 100-
EXPANDS TO (KVAR)475
DIMENSIONS (MM)(H) 2180 x (W) 600 x (D) 630